The instrument is the Central Electricity Authority (Measures relating to Safety and Electric Supply) Amendment Regulations, 2026, which introduces a safety framework for battery energy storage systems as a new chapter. It takes effect from 1 April 2027, and its provisions apply to installations operating above 650 volts.
The reported requirements include a two-fault tolerance design principle, monitoring and recording by the battery management system of voltage, temperature and thermal runaway at cell, module and rack level, and of current at rack level, with audio-visual alarms when a monitored parameter leaves the manufacturer's operating range and charge and discharge stopped when temperature exceeds the manufacturer's recommended values, hazard detection covering smoke, gas, heat and flame, automatic fire suppression in battery containers, forced ventilation and explosion protection, HVAC for thermal management, and physical security including fencing of at least 1.8 metres with CCTV. An independent third-party fire safety audit is required within three months of the regulations coming into force, with the report submitted to the Electrical Inspector.
That paragraph is a summary of published reporting on the amendment, and it is offered as an orientation rather than as a compliance position. An operational reading of what those requirements imply for measurement follows, and that reading is analysis rather than regulation. Anyone making a design or compliance decision should work from the notified text and their Electrical Inspector's guidance, not from this page or from any other summary.